Paper Lifetime Mathematical Modelling based on Multi Pre-Exponential Factors for Oil-Immersed Transformer

Najiyah Saleh, Norhafiz Azis, Jasronita Jasni, Mohd Zainal Abidin Ab Kadir and Mohd Aizam Talib

Pertanika Journal of Social Science and Humanities, Volume 30, Issue 2, April 2022

DOI: https://doi.org/10.47836/pjst.30.2.15

Keywords: Arrhenius equation, cellulose ageing, life estimation, paper ageing, pre-exponential factor

Published on: 1 April 2022

This work examines the impact of multi pre-exponential factors on the lifetime modelling of the paper in oil-immersed transformers. First, the corresponding pre-exponential factor was determined based on the concentrations of the three parameters known as oxygen, moisture and acid. Next, the pre-exponential factor for each of the parameters at different concentrations was combined based on the summative approach to obtain the overall impact on the lifetime of the paper. It is found that the expected life of the paper for overall multi pre-exponential factors is higher than either single or double pre-exponential factors. For a single pre-exponential factor, the expected life of the paper decreases by a factor of 59.8 as the oxygen concentration increases from 15,000 ppm to 210,000 ppm. Moisture can decrease the expected life of the paper by a factor of 34 as it increases from 0.5% to 5%. Low molecular weight acid (LMA) has a higher impact than high molecular weight acid (HMA), whereby its impact is further enhanced through multi pre-exponential factor effect whereby the expected life of the paper decreases by a factor of 7.9 as the moisture content increases from 0.5% to 5% and oxygen increases from 300 ppm to 20,000 ppm.

  • Arrhenius, S. (1889). On the reaction rate of the inversion of non-refined sugar upon souring. Zeitschrift Für Physikalische Chemie, 4U(1), 226-248.

  • British Standards Institution. (2018). BS IEC 60076-7:2018 Power transformers. Loading guide for mineral-oil-immersed power transformers. British Standards Institution.

  • Boyes, W. (2010). Instrumentation reference book. Elsevier Science. https://doi.org/10.1016C2009-0-25186-5

  • CIGRE Brochure. (2007). Ageing of cellulose in mineral-oil insulated transformers. CIGRE Publication.

  • CIGRE Brochure. (2009). Thermal performance of transformers. CIGRE Publication.

  • Ekenstam, A. (1936). The behaviour of cellulose in mineral acid solutions: Kinetic study of the decomposition of cellulose in acid solutions. Berichte Der Deutschen Chemischen Gesellschaft, 69, 553-559.

  • Emsley, A. M., & Stevens, G. C. (1994a). Kinetics and mechanisms of the low-temperature degradation of cellulose. Cellulose, 1, 26-56. https://doi.org/10.1007/BF00818797

  • Emsley, A. M., & Stevens, G. C. (1994b). Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers. IEE Proceedings-Science, Measurement and Technology, 141(5), 324-334. https://doi.org/10.1049/ip-smt:19949957

  • Emsley, A. M., Heywood, R. J., Ali, M., & Xiao, X. (2000a). Degradation of cellulosic insulation in power transformers. Part 4: Effects of ageing on the tensile strength of paper. IEE Proceedings-Science, Measurement and Technology, 147(6), 285-290. https://doi.org/10.1049/ip-smt:20000644

  • Emsley, A. M., Xiao, X., Heywood, R. J., & Ali, M. (2000b). Degradation of cellulosic insulation in power transformers. Part 2: Formation of furan products in insulating oil. IEE Proceedings-Science, Measurement and Technology, 147(3), 110-114. https://doi.org/10.1049/ip-smt:20000259

  • Emsley, A. M., Xiao, X., Heywood, R. J., & Ali, M. (2000c). Degradation of cellulosic insulation in power transformers. Part 3: Effects of oxygen and water on ageing in oil. IEE Proceedings-Science, Measurement and Technology, 147(3), 115-119. https://doi.org/10.1049/ip-smt:20000021

  • Ese, M. H. G., Liland, K. B., & Lundgaard, L. E. (2010). Oxidation of paper insulation in transformers. IEEE Transactions on Dielectrics and Electrical Insulation, 17(3), 939-946. https://doi.org/10.1109/TDEI.2010.5492270

  • Feng, D. (2013). Life expectancy investigation of transmission power transformers. University of Manchester.

  • Gasser, H. P., Huser, J., Krause, C., Dahinden, V., & Emsley, A. M. (1999). Determining the ageing parameters of cellulosic insulation in a transformer. In 1999 Eleventh International Symposium on High Voltage Engineering (Vol. 4, pp. 143-147). IET Publishing. https://doi.org/10.1049/cp:19990813

  • Heywood, R. J., Emsley, A. M., & Ali, M. (2000). Degradation of cellulosic insulation in power transformers. Part 1: Factors affecting the measurement of the average viscometric degree of polymerisation of new and aged electrical papers. IEE Proceedings-Science, Measurement and Technology, 147(2), 86-90. https://doi.org/10.1049/ip-smt:20000076

  • Hill, D. J. T., Le, T. T., Darveniza, M., & Saha, T. (1995). A study of the degradation of cellulosic insulation materials in a power transformer. Part 2: Tensile strength of cellulose insulation paper. Polymer Degradation and Stability, 49(3), 429-435. https://doi.org/10.1016/0141-3910(95)00204-9

  • Kim, J. H., Park, D. K., & Han, S. O. (2010). Estimation for degradation characteristics of cellulose paper used in oil-filled transformer and analysis for correlationship using statistical treatment. In Conference on Precision Electromagnetic Measurements (CPEM 2010) (pp. 692-693). IEEE Publishing. https://doi.org/10.1109/CPEM.2010.5544170

  • Lelekakis, N., Guo, W., Martin, D., Wijaya, J., & Susa, D. (2012a). A field study of aging in paper-oil insulation systems. IEEE Electrical Insulation Magazine, 28(1), 12-19. https://doi.org/10.1109/MEI.2012.6130527

  • Lelekakis, N., Martin, D., & Wijaya, J. (2012b). Ageing rate of paper insulation used in power transformers part 1: Oil/paper system with low oxygen concentration. IEEE Transactions on Dielectrics and Electrical Insulation, 19(6), 1999-2008. https://doi.org/10.1109/TDEI.2012.6396958

  • Lelekakis, N., Martin, D., & Wijaya, J. (2012c). Ageing rate of paper insulation used in power transformers part 2: Oil/paper system with medium and high oxygen concentration. IEEE Transactions on Dielectrics and Electrical Insulation, 19(6), 2009-2018. https://doi.org/10.1109/TDEI.2012.6396960

  • Lundgaard, L. E., Hansen, W., & Ingebrigtsen, S. (2008). Ageing of mineral oil impregnated cellulose by acid catalysis. IEEE Transactions on Dielectrics and Electrical Insulation, 15(2), 540-546. https://doi.org/10.1109/TDEI.2008.4483475

  • Lundgaard, L. E., Hansen, W., Ingebrigtsen, S., Linhjell, D., & Dahlund, M. (2005). Aging of kraft paper by acid catalyzed hydrolysis. In IEEE International Conference on Dielectric Liquids (ICDL 2005) (pp. 381-384). IEEE Publishing. https://doi.org/10.1109/ICDL.2005.1490105

  • Lundgaard, L. E., Hansen, W., Linhjell, D., & Painter, T. J. (2004). Aging of oil-impregnated paper in power transformers. IEEE Transactions on Power Delivery, 19(1), 230-239. https://doi.org/10.1109/TPWRD.2003.820175

  • Martin, D., Cui, Y., Saha, T., Lelekakis, N., & Wijaya, J. (2013). Life estimation techniques for transformer insulation. In 2013 Australasian Universities Power Engineering Conference (AUPEC) (pp. 1-6). IEEE Publishing. https://doi.org/10.1109/AUPEC.2013.6725457

  • Martin, D., Cui, Y., Ekanayake, C., Ma, H., & Saha, T. (2015). An updated model to determine the life remaining of transformer insulation. IEEE Transactions on Power Delivery, 30(1), 395-402. https://doi.org/10.1109/TPWRD.2014.2345775

  • Mirzaie, M., Gholami, A., & Tayyebi, H. (2007). Thermal degradation of cellulose paper insulation in power transformers. In 2007 IEEE International Conference on Solid Dielectrics (pp. 673-676). IEEE Publishing. https://doi.org/10.1109/ICSD.2007.4290903

  • Redline, S. (2012). IEEE Guide for loading mineral-oil-immersed transformers and step-voltage regulators. IEEE Power & Energy Society. https://doi.org/10.1109/ieeestd.2012.6166928

  • Susa, D., Liland, K. B., Lundgaard, L., & Vardal, G. (2011). Generator step-up transformer post mortem assessment. European Transactions on Electrical Power, 21(5), 1802-1822. https://doi.org/10.1002/etep.544

  • Teymouri, A., & Vahidi, B. (2019). Estimation of power transformer remaining life from activation energy and pre-exponential factor in the Arrhenius equation. Cellulose, 26(18), 9709-9720. https://doi.org/10.1007/s10570-019-02746-w

  • Verma, P., Roy, M., Tiwari, R. K., & Chandra, S. (2005). Generation of furanic compounds in transformer oil under accelerated thermal and electrical stress. In Proceedings Electrical Insulation Conference and Electrical Manufacturing Expo, 2005 (pp. 112-116). IEEE Publishing. https://doi.org/10.1109/EEIC.2005.1566270